Eni ITE 600

Straight mineral electrical insulating oil for transformers

Business customers only. We sell wholesale, invoiced to registered companies.

Standards & approvals

  • IEC 60296, Type B — inhibited transformer oil

    Type B of IEC 60296: a mineral insulating oil for transformers with an added oxidation inhibitor.

The whole Eni ITE range

Specifications

Brand
Eni
Range
Eni ITE
Type
Mineral oils
Manufacturer code
004416
Availability
On request

Typical characteristics

PropertyTypical valueMethod
Appearanceclear
Density at 20°Ckg/m³870ASTM D 1298
Viscosity at 40°Cmm²/s10ASTM D 445
Flash point PM°C150ASTM D 93
Pour point°C-48ASTM D 97
Mean Breakdown voltage after TreatmentkV>70IEC 60156
Mean Breakdown voltagekV50IEC 60156

Complete documentation

Manufacturer's description

Eni ITE 600 is a high quality, straight (unadditivated) mineral electrical insulating oil, which can be used in transformers, circuit breakers, capacitors, rheostats and other electrical applications where low temperatures are met.

Applications

  • Used in transformers, switchgear, condensers, rheostats and many other electrical applications, including where particularly low temperatures can occur.

Performance & benefits

  • Suitable for transformers operating at very low temperatures thanks to its low pour point
  • Non-corrosive towards copper, with no need for passivation
  • Outstanding protection against electrical discharges thanks to excellent dielectric strength
  • Good heat-transfer properties
  • Long drain intervals thanks to outstanding resistance to thermal and chemical degradation
  • Highly stable; meets the corrosion requirements of the ASTM D1275B / CIGRE TF A2.32.01 (CCD) tests

Fits

Frontier I.G. offers a complete range of solutions across mobility as a whole. Leading lubricants, tyres and innovative technical solutions for automotive, industry and agriculture.

About Frontier

Where should the files go?