- Transformers
IEC 60296 Type A
Straight mineral electrical insulating oil for transformers
Business customers only. We sell wholesale, invoiced to registered companies.
IEC 60296, Type B — inhibited transformer oil
Type B of IEC 60296: a mineral insulating oil for transformers with an added oxidation inhibitor.
| Property | Typical value | Method |
|---|---|---|
| Appearance | clear | |
| Density at 20°Ckg/m³ | 870 | ASTM D 1298 |
| Viscosity at 40°Cmm²/s | 10 | ASTM D 445 |
| Flash point PM°C | 150 | ASTM D 93 |
| Pour point°C | -48 | ASTM D 97 |
| Mean Breakdown voltage after TreatmentkV | >70 | IEC 60156 |
| Mean Breakdown voltagekV | 50 | IEC 60156 |

Eni ITE 600 is a high quality, straight (unadditivated) mineral electrical insulating oil, which can be used in transformers, circuit breakers, capacitors, rheostats and other electrical applications where low temperatures are met.
Frontier I.G. offers a complete range of solutions across mobility as a whole. Leading lubricants, tyres and innovative technical solutions for automotive, industry and agriculture.